Waste-Heat Recovery Loops for District Heating from Compute Halls
Beatriz Quintanilla, Tariq Al-Mansouri
We couple the return loop of a liquid-cooled hall to a district heating network through a heat pump with variable lift. A control strategy keeps the supply temperature within the network contract while following compute load. Over a heating season the loop delivered the equivalent of the winter demand of eight hundred homes.
Stability Margins for Controllers with Heavy-Tailed Disturbances
Classical stability margins assume bounded or Gaussian disturbances. Using an averaging result for systems driven by stable noise, we define a margin that is meaningful when disturbances have infinite variance and give a test for it. Case studies on a hovering platform and a cooling loop show that the usual margins overstate robustness.
Thermal Energy Storage for Free-Cooling Extension
We store coolant chilled by free cooling overnight in stratified tanks and discharge it through the warm part of the day, extending economiser hours at climates where they would otherwise run out. A scheduling model sizes the tank against the forecast. A demonstration hall achieved twenty-two percent more free-cooling hours than the same hall without storage.
Datacentre Thermal Control under Heavy-Tailed Load Surges
Tariq Al-Mansouri, Beatriz Quintanilla
Compute load in a datacentre arrives in surges whose size is heavy-tailed, and cooling controllers tuned for typical load overheat during rare spikes. We apply an averaged-dynamics model and the tail-aware stability margin to set cooling headroom, and test the design on two production halls. Peak inlet temperature excursions fall by sixty percent for a four percent rise in cooling energy.