  1. Battery Energy Storage Sizing for Datacentre Ride-Through

    Tariq Al-Mansouri

    We size battery storage for a datacentre by minimising lifetime cost subject to a ride-through requirement and a model of capacity fade. Outage statistics from the regional grid enter as a chance constraint. The resulting capacity is thirty percent below the usual worst-case rule at the same availability.

    ENGJournal of RMH Engineering2019Cited by 3Resonance 3