Archive
168 papers in twelve fields, 2011 to 2026. Search titles, authors, keywords and abstracts.
Results
Free-Cooling Economisers under Variable Humidity
Outside-air economisers save energy but are limited by humidity. We model the hours of free cooling available at a site as a function of an allowable humidity envelope and show how adiabatic assist extends them. A year of operating data from two halls confirms the predicted savings within five percent.
Thermal Energy Storage for Free-Cooling Extension
We store coolant chilled by free cooling overnight in stratified tanks and discharge it through the warm part of the day, extending economiser hours at climates where they would otherwise run out. A scheduling model sizes the tank against the forecast. A demonstration hall achieved twenty-two percent more free-cooling hours than the same hall without storage.