Archive
168 papers in twelve fields, 2011 to 2026. Search titles, authors, keywords and abstracts.
Results
Waste-Heat Recovery Loops for District Heating from Compute Halls
Beatriz Quintanilla, Tariq Al-Mansouri
We couple the return loop of a liquid-cooled hall to a district heating network through a heat pump with variable lift. A control strategy keeps the supply temperature within the network contract while following compute load. Over a heating season the loop delivered the equivalent of the winter demand of eight hundred homes.
Waste Heat Reuse from Liquid-Cooled Facilities in District Networks
Liquid cooling returns heat at 50 to 60 degrees Celsius, high enough to feed low-temperature district networks without heat pumps. We model supply and demand matching for 14 cities and find that a single 20 MW facility can cover the winter heating load of up to 9,000 homes. Seasonal mismatch is the binding constraint, not temperature.