3 results

  1. Free-Cooling Economisers under Variable Humidity

    Beatriz Quintanilla

    Outside-air economisers save energy but are limited by humidity. We model the hours of free cooling available at a site as a function of an allowable humidity envelope and show how adiabatic assist extends them. A year of operating data from two halls confirms the predicted savings within five percent.

    ENGJournal of RMH Engineering2013Cited by 7Resonance 6

  2. Free-Cooling Hours Under Shifting Humid-Heat Regimes

    Soo-jin Han

    We project the annual number of hours in which outside air or water can reject facility heat without mechanical chilling, for 220 sites to 2060. Humid-heat extremes erode free-cooling hours faster than mean warming suggests, and fluids with higher operating temperatures preserve most of the margin. Coolant stability under thermal cycling is a limiting factor in the warmest regimes.

    EARTHRMH Geophysical Letters2025Cited by 1Resonance 2

  3. Thermal Energy Storage for Free-Cooling Extension

    Beatriz Quintanilla, Anh Tran

    We store coolant chilled by free cooling overnight in stratified tanks and discharge it through the warm part of the day, extending economiser hours at climates where they would otherwise run out. A scheduling model sizes the tank against the forecast. A demonstration hall achieved twenty-two percent more free-cooling hours than the same hall without storage.

    ENGJournal of RMH Engineering2026Cited by 0Resonance 0