Archive
168 papers in twelve fields, 2011 to 2026. Search titles, authors, keywords and abstracts.
Results
Non-Flammable Dielectric Coolants from Fluorinated Ethers
Anahita Farahmand, Mei-Ling Zhou
We synthesise a family of partially fluorinated ethers with boiling points tuned between 45 and 70 degrees Celsius for two-phase immersion cooling. The best candidate combines a latent heat of 110 kJ per kilogram, no measurable flash point and low global warming potential. Heat transfer on structured copper surfaces matches that of established coolants.
Coolant Maldistribution in Parallel Cold Plates under Transient Load
When many cold plates share a manifold, a sudden load step redistributes flow in ways that steady-state design ignores. We derive a lumped-parameter model of the manifold-plate network and validate it against a 48-plate test loop. Flow to the most heavily loaded plate lags its heat demand by up to nine seconds, and a feed-forward valve schedule removes the lag.
Waste Heat Reuse from Liquid-Cooled Facilities in District Networks
Liquid cooling returns heat at 50 to 60 degrees Celsius, high enough to feed low-temperature district networks without heat pumps. We model supply and demand matching for 14 cities and find that a single 20 MW facility can cover the winter heating load of up to 9,000 homes. Seasonal mismatch is the binding constraint, not temperature.
Heat Spreading in Graphene-Copper Laminates for Server Cold Plates
Graphene-copper laminates spread heat anisotropically, and we show how to exploit this in cold plates over processors with strongly non-uniform dissipation. A conduction model with interfacial resistance predicts peak junction temperature to within 1.5 K. A 40 percent reduction in hot-spot temperature rise is obtained with a 12 percent mass penalty.