Coolant Maldistribution in Parallel Cold Plates under Transient Load
Abstract
When many cold plates share a manifold, a sudden load step redistributes flow in ways that steady-state design ignores. We derive a lumped-parameter model of the manifold-plate network and validate it against a 48-plate test loop. Flow to the most heavily loaded plate lags its heat demand by up to nine seconds, and a feed-forward valve schedule removes the lag.
Cite
Reference
Zhou, M. (2025). Coolant Maldistribution in Parallel Cold Plates under Transient Load. RMH Journal of Thermal Physics.