Two-Phase Immersion Cooling of Dense Compute Racks: A Transport Model
Abstract
We derive a reduced transport model for two-phase immersion cooling of racks dissipating over 80 kW. The model couples bubble departure, vapour channelling between boards and condenser capacity, and predicts the onset of dry-out within 6 percent of bench measurements. It gives a rack-level design rule for board pitch as a function of power density.