Coolant Degradation Under Repeated Thermal Cycling in Immersion Systems
Abstract
Immersion coolants experience thousands of boil-condense cycles over a service life. We track acidity, dissolved fluoride and dielectric strength of a fluorinated ether coolant through 20,000 accelerated cycles and find that trace water drives the degradation. A molecular-sieve loop holds fluoride below the corrosion threshold.
Cite
Reference
Farahmand, A. (2025). Coolant Degradation Under Repeated Thermal Cycling in Immersion Systems. RMH Materials Chemistry.
BibTeX
@article{farahmand2025coolantdegra,
title = {Coolant Degradation Under Repeated Thermal Cycling in Immersion Systems},
author = {Anahita Farahmand},
journal = {RMH Materials Chemistry},
year = {2025},
url = {https://rmhstudios.com/rmh-research/paper/coolant-degradation-thermal-cycling}