Two-Phase Immersion Cooling of Dense Compute Racks: A Transport Model
We derive a reduced transport model for two-phase immersion cooling of racks dissipating over 80 kW. The model couples bubble departure, vapour channelling between boards and condenser capacity, and predicts the onset of dry-out within 6 percent of bench measurements. It gives a rack-level design rule for board pitch as a function of power density.
Coolant Degradation Under Repeated Thermal Cycling in Immersion Systems
Immersion coolants experience thousands of boil-condense cycles over a service life. We track acidity, dissolved fluoride and dielectric strength of a fluorinated ether coolant through 20,000 accelerated cycles and find that trace water drives the degradation. A molecular-sieve loop holds fluoride below the corrosion threshold.
Non-Flammable Dielectric Coolants from Fluorinated Ethers
Anahita Farahmand, Mei-Ling Zhou
We synthesise a family of partially fluorinated ethers with boiling points tuned between 45 and 70 degrees Celsius for two-phase immersion cooling. The best candidate combines a latent heat of 110 kJ per kilogram, no measurable flash point and low global warming potential. Heat transfer on structured copper surfaces matches that of established coolants.
Cooling Water Demand Under Warming: Basin-Scale Withdrawal Projections
We project industrial cooling water withdrawal for 60 river basins under four warming scenarios using a model that couples wet-bulb temperature, plant type and water allocation rules. Withdrawals rise by 18 to 41 percent by 2050 for evaporative systems. Closed-loop and immersion alternatives reduce the exposure substantially.
Siting Large Thermal Loads Against Regional Climate Risk
Large facilities that reject megawatts of heat are exposed to the regional climate for decades. We build a siting framework that scores locations on projected wet-bulb extremes, water availability and seismic hazard, and apply it to 220 candidate sites. Liquid and immersion cooling shift the preferred sites toward hotter, drier regions that would be ruled out under evaporative cooling.