  1. Coolant Degradation Under Repeated Thermal Cycling in Immersion Systems

    Anahita Farahmand

    Immersion coolants experience thousands of boil-condense cycles over a service life. We track acidity, dissolved fluoride and dielectric strength of a fluorinated ether coolant through 20,000 accelerated cycles and find that trace water drives the degradation. A molecular-sieve loop holds fluoride below the corrosion threshold.

    CHEMRMH Materials Chemistry2025Cited by 1Resonance 2

  2. Non-Flammable Dielectric Coolants from Fluorinated Ethers

    Anahita Farahmand, Mei-Ling Zhou

    We synthesise a family of partially fluorinated ethers with boiling points tuned between 45 and 70 degrees Celsius for two-phase immersion cooling. The best candidate combines a latent heat of 110 kJ per kilogram, no measurable flash point and low global warming potential. Heat transfer on structured copper surfaces matches that of established coolants.

    CHEMRMH Materials Chemistry2024Cited by 3Resonance 4

  3. Siting Large Thermal Loads Against Regional Climate Risk

    Baraka Mwangi

    Large facilities that reject megawatts of heat are exposed to the regional climate for decades. We build a siting framework that scores locations on projected wet-bulb extremes, water availability and seismic hazard, and apply it to 220 candidate sites. Liquid and immersion cooling shift the preferred sites toward hotter, drier regions that would be ruled out under evaporative cooling.