Archive
168 papers in twelve fields, 2011 to 2026. Search titles, authors, keywords and abstracts.
Results
Nucleate Boiling Heat Flux on Micro-Structured Copper Surfaces
We characterise pool boiling of a dielectric fluid on copper surfaces patterned with micro-pillar arrays of varying pitch. Critical heat flux rises by up to 70 percent over a smooth surface, and the gain collapses onto a single curve once the pillar pitch is scaled by the capillary length. A hydrodynamic model of vapour escape paths explains the optimum.
Waste-Heat Recovery Loops for District Heating from Compute Halls
Beatriz Quintanilla, Tariq Al-Mansouri
We couple the return loop of a liquid-cooled hall to a district heating network through a heat pump with variable lift. A control strategy keeps the supply temperature within the network contract while following compute load. Over a heating season the loop delivered the equivalent of the winter demand of eight hundred homes.
Free-Cooling Hours Under Shifting Humid-Heat Regimes
We project the annual number of hours in which outside air or water can reject facility heat without mechanical chilling, for 220 sites to 2060. Humid-heat extremes erode free-cooling hours faster than mean warming suggests, and fluids with higher operating temperatures preserve most of the margin. Coolant stability under thermal cycling is a limiting factor in the warmest regimes.
Compound Heat and Drought Events in Reanalysis Ensembles
Compound heat and drought events are more frequent than independence would imply. In a five-reanalysis ensemble the co-occurrence rate is 1.8 times the independent expectation over mid-latitude land, and it is rising. Soil-moisture feedback accounts for roughly two thirds of the excess.
Waste Heat Reuse from Liquid-Cooled Facilities in District Networks
Liquid cooling returns heat at 50 to 60 degrees Celsius, high enough to feed low-temperature district networks without heat pumps. We model supply and demand matching for 14 cities and find that a single 20 MW facility can cover the winter heating load of up to 9,000 homes. Seasonal mismatch is the binding constraint, not temperature.
Heat Spreading in Graphene-Copper Laminates for Server Cold Plates
Graphene-copper laminates spread heat anisotropically, and we show how to exploit this in cold plates over processors with strongly non-uniform dissipation. A conduction model with interfacial resistance predicts peak junction temperature to within 1.5 K. A 40 percent reduction in hot-spot temperature rise is obtained with a 12 percent mass penalty.
Spinon Heat Transport in a Kagome Quantum Spin Liquid Candidate
We measure the low-temperature thermal conductivity of a kagome quantum spin liquid candidate down to 40 mK and find a residual linear term consistent with itinerant gapless excitations. The magnitude is sensitive to sample disorder in a way not seen in the thermal Hall channel. We discuss implications for the spinon Fermi-surface scenario.
Non-Flammable Dielectric Coolants from Fluorinated Ethers
Anahita Farahmand, Mei-Ling Zhou
We synthesise a family of partially fluorinated ethers with boiling points tuned between 45 and 70 degrees Celsius for two-phase immersion cooling. The best candidate combines a latent heat of 110 kJ per kilogram, no measurable flash point and low global warming potential. Heat transfer on structured copper surfaces matches that of established coolants.
Wet-Bulb Temperature Extremes in Humid Subtropical Cities
We analyse hourly wet-bulb temperature in 40 humid subtropical cities and find that annual extremes have risen by 0.6 degrees Celsius per decade, faster than dry-bulb extremes. Urban form modifies the extremes by up to 1.5 degrees. The record implies a shrinking margin for evaporative cooling systems.
Thermal Hall Response of Kagome Magnets
We report a large thermal Hall conductivity in an insulating kagome magnet that persists well above the ordering temperature. The signal exceeds the phonon estimate by an order of magnitude and tracks the field-induced canting angle. We propose a magnon-edge-current mechanism arising from the lattice geometry.
Soil Moisture Memory and Heatwave Persistence
Dry soils amplify surface heating, but the length of this memory has been uncertain. Using a land-atmosphere coupled ensemble we show that a soil-moisture deficit in late spring extends the median heatwave by 2.3 days. The effect saturates once the root zone is depleted below a threshold fraction.
Floquet Prethermalization Lifetimes Beyond Linear Response
The heating time of a periodically driven many-body system grows exponentially with drive frequency, but the prefactor has resisted calculation. We obtain it for a family of spin chains by resumming the high-frequency expansion past linear response. The lifetime predictions agree with numerics at drive amplitudes where earlier bounds are vacuous.
Microchannel Flow Boiling Instability Thresholds
Parallel microchannels under flow boiling develop pressure-drop oscillations that couple to the supply loop. We map the stability boundary in the plane of heat flux and inlet subcooling and show that a modest inlet restriction suppresses the oscillation without a measurable pumping penalty. The thresholds collapse under a single dimensionless group.
Siting Large Thermal Loads Against Regional Climate Risk
Large facilities that reject megawatts of heat are exposed to the regional climate for decades. We build a siting framework that scores locations on projected wet-bulb extremes, water availability and seismic hazard, and apply it to 220 candidate sites. Liquid and immersion cooling shift the preferred sites toward hotter, drier regions that would be ruled out under evaporative cooling.
Model Predictive Control of Coupled Thermal Zones
We formulate cooling of thermally coupled zones as a receding-horizon problem whose model captures heat exchange between neighbouring halls. A distributed solver keeps the computation local to each zone with a bounded optimality loss. Closed-loop tests show a reduction in temperature variance relative to decentralised PID control.
Coolant Maldistribution in Parallel Cold Plates under Transient Load
When many cold plates share a manifold, a sudden load step redistributes flow in ways that steady-state design ignores. We derive a lumped-parameter model of the manifold-plate network and validate it against a 48-plate test loop. Flow to the most heavily loaded plate lags its heat demand by up to nine seconds, and a feed-forward valve schedule removes the lag.
Quantum Critical Scaling in a Layered Nickelate Analogue
Resistivity and specific heat of a layered nickelate analogue collapse onto a single scaling function near a pressure-tuned quantum critical point. The extracted dynamical exponent is close to 1.5, inconsistent with the simplest itinerant spin-density-wave theory. We discuss the role of interlayer coupling in setting the crossover.